www.rkiinstruments.com35-3001-06-01Combustible Gas/OxygenSample-Draw DetectorOperator’s ManualPart Number: 71-0292RKRevision: P7Released: 9/17/14
6 • 35-3001-06-01 Combustible Gas/Oxygen Sample-Draw DetectorInstallationThis section describes procedures to mount the sample-draw detector in the m
35-3001-06-01 Combustible Gas/Oxygen Sample-Draw Detector • 72. Close and latch the housing door.NOTE: The sample-draw detector is shipped with the
8 • 35-3001-06-01 Combustible Gas/Oxygen Sample-Draw Detectorring, if it came out, in the orientation shown in Figure 4. 4. Screw the inlet fitting t
35-3001-06-01 Combustible Gas/Oxygen Sample-Draw Detector • 9Installing the Exhaust Line1. Loosen the nut on the exhaust fitting until 3 threads are
10 • 35-3001-06-01 Combustible Gas/Oxygen Sample-Draw Detector8. Connect the wires to the applicable detector/transmitter terminal strip at the contr
35-3001-06-01 Combustible Gas/Oxygen Sample-Draw Detector • 11Start UpThis section describes procedures to start up the sample-draw detector and pla
12 • 35-3001-06-01 Combustible Gas/Oxygen Sample-Draw Detectorreading is not 0 %LEL for the combustible channel or 20.9% for the oxygen channel, cont
35-3001-06-01 Combustible Gas/Oxygen Sample-Draw Detector • 132. Connect the calibration tubing from the demand flow regulator to the inlet fitting.
14 • 35-3001-06-01 Combustible Gas/Oxygen Sample-Draw Detector4. Calibrate the sample-draw detector as described in “Calibration, IR LEL Sensor” on p
35-3001-06-01 Combustible Gas/Oxygen Sample-Draw Detector • 158. Secure the sensor PCB on the flow block with the four screws you removed in step 4.
35-3001-06-01 Combustible Gas/Oxygen Sample-Draw DetectorWARNINGRead and understand this instruction manual before operating detector. Improper use o
16 • 35-3001-06-01 Combustible Gas/Oxygen Sample-Draw Detector4. Reinstall the tubing routed to the sampling area.Adjusting the Low Flow SettingNOTE:
35-3001-06-01 Combustible Gas/Oxygen Sample-Draw Detector • 17Calibration, IR LEL SensorThis section describes how to calibrate the IR combustible g
18 • 35-3001-06-01 Combustible Gas/Oxygen Sample-Draw DetectorCalibration, Oxygen SensorThis section describes how to calibrate the oxygen sensor in
35-3001-06-01 Combustible Gas/Oxygen Sample-Draw Detector • 192. Verify that the controller display reading stabilizes at 20.9%.3. Store the compone
35-3001-06-01 Combustible Gas/Oxygen Sample-Draw DetectorProduct WarrantyRKI Instruments, Inc. warrants gas alarm equipment sold by us to be free fr
35-3001-06-01 Combustible Gas/Oxygen Sample-Draw DetectorTable of ContentsOverview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
35-3001-06-01 Combustible Gas/Oxygen Sample-Draw Detector • 1OverviewThis operator’s manual describes the 35-3001-06-01 combustible gas/oxygen sampl
2 • 35-3001-06-01 Combustible Gas/Oxygen Sample-Draw DetectorDescriptionThis section describes the components of the combustible gas/oxygen sample-dr
35-3001-06-01 Combustible Gas/Oxygen Sample-Draw Detector • 3installation where general purpose equipment is in use.The housing door is hinged on th
4 • 35-3001-06-01 Combustible Gas/Oxygen Sample-Draw DetectorDetector/Amp Terminal StripThe detector/amp terminal strip is the upper twelve-point ter
35-3001-06-01 Combustible Gas/Oxygen Sample-Draw Detector • 5Sensor Flow Control ValveThe sensor flow control valve is mounted to the flowmeter circ