www.rkiinstruments.com35-3010RK-07 Sample-DrawDetectorPart Number: 71-0214RKRevision: BReleased: 9/10/12
6 • 35-3010RK-07 Sample-Draw DetectorMain Circuit BoardFigure 3: Main Circuit BoardThe main circuit board includes the interconnect terminal strip,
35-3010RK-07 Sample-Draw Detector • 7Amp 1 and Amp 2 CircuitsThese circuits are located to the left of the sensor/transmitter terminal strip. They ea
8 • 35-3010RK-07 Sample-Draw DetectorInstallationThis section describes procedures to mount the sample draw gas detector in the monitoring environmen
35-3010RK-07 Sample-Draw Detector • 96. Position the sample draw housing on a vertical surface at eye level (4 1/2 to 5 feet from the floor).7. Inser
10 • 35-3010RK-07 Sample-Draw DetectorFigure 5: External (Field) Wiring, Sample Draw DetectorH2S(Controller TransmitterTerminals)24 VDC -24 VDC +Int
35-3010RK-07 Sample-Draw Detector • 11Figure 6: Internal (Factory) Wiring, Sample Draw DetectorOxygen SensorH2SH2S SensorPlugs IntoFar Side of Pream
12 • 35-3010RK-07 Sample-Draw DetectorStart UpThis section describes procedures to start up the sample draw detector and place the sample draw detect
35-3010RK-07 Sample-Draw Detector • 13the controller instruction manual for directions.6. Verify a reading of 20.9% oxygen for the oxygen channel at
14 • 35-3010RK-07 Sample-Draw DetectorMonthlyThis procedure describes a test to verify that the sample draw detector responds properly to the target
35-3010RK-07 Sample-Draw Detector • 15Probable Causes• The sample draw detector’s flow rate is too low because of an obstructed sample line, failed p
35-3010RK-07 Sample-Draw DetectorWARNINGRead and understand this instruction manual before operating detector. Improper use of the detector could res
16 • 35-3010RK-07 Sample-Draw DetectorReplacing Components of the Sample Draw DetectorThis section includes procedures to replace the sensors, the hy
35-3010RK-07 Sample-Draw Detector • 179. Calibrate the replacement sensor as described in “Store the components of the calibration kit in a safe and
18 • 35-3010RK-07 Sample-Draw DetectorCalibration FrequencyAlthough there is no particular calibration frequency that is correct for all applications
35-3010RK-07 Sample-Draw Detector • 19Setting the Zero ReadingNOTE: If you can verify a fresh air environment, it is not necessary to use a zero air
20 • 35-3010RK-07 Sample-Draw DetectorCalibration, IR CH4 DetectorThis section describes how to calibrate the IR CH4 sensor in the sample draw detect
35-3010RK-07 Sample-Draw Detector • 21Returning to Normal Operation1. Reconnect the incoming sample line.2. Wait 1 to 2 minutes to allow the calibrat
22 • 35-3010RK-07 Sample-Draw DetectorSetting the Fresh Air ReadingCAUTION: This procedure may cause alarms at the controller. Take appropriate actio
35-3010RK-07 Sample-Draw Detector • 23Parts ListTable 4 lists replacement parts and accessories for the sample draw gas detector.Table 2: Parts ListP
35-3010RK-07 Sample-Draw DetectorProduct WarrantyRKI Instruments, Inc. warrants gas alarm equipment sold by us to be free from defects in materials,
35-3010RK-07 Sample-Draw DetectorTable of ContentsOverview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
35-3010RK-07 Sample-Draw Detector • 1OverviewThis manual describes the 35-3010RK-07 sample draw detector. This manual also describes how to install,
2 • 35-3010RK-07 Sample-Draw DetectorDescriptionThis section describes the components of the 35-3010RK-07 sample draw detector. The sample draw detec
35-3010RK-07 Sample-Draw Detector • 3Flow SystemThe sample draw detector’s flow system consists of the INLET fitting, hydrophobic filter, charcoal fi
4 • 35-3010RK-07 Sample-Draw DetectorCharcoal FilterThe charcoal filter is located in the top left corner of the enclosure. It is held in place by a
35-3010RK-07 Sample-Draw Detector • 5Flow BlocksBoth flow blocks are located in the lower right corner of the sample-draw detector. The oxygen and H2